ELIGHT constant current regulators
are expressly developed for the power supply of lamp series
circuits dedicated to public lighting systems, conforming
to the directives in force.
Constant Current Regulators, ELIGHT CCR series, are outcome
of a long experience static frequency converter both civil
and military field (receiving the NATO code for the quality
of his supplies).
All of our equipments distinguish themselves by the employment
of advanced technological components, excellent reliability
and easy maintenance.
The simplicity of working is the main feature of all of our
products.
Principles of working
The ELIGHT CCR Constant Current Regulator has the purpose
to feed to series circuits a constant and sinusoidal current.
The rectifier transforms the input alternate voltage in direct
voltage, then the IGBT inverter transforms the dc voltage
in alternate and sinusoidal current with a PWM modulation
(Pulse Width Modulation).
With the ELIGHT CCR, keeping constant the current, the lamps
don’t feel the effect of reduction of the brightness
for getting old, neither for drop line voltage nor for cold
temperatures. Features
- Input power factor at full load > 0.95;
- Efficiency > 90%;
- Energy saving with reduction of luminous flux;
- Reduced cable cross section of plant system (9.6A or 20A):
up to 100kVA;
- Absence of any stress on electrodes lamp during ignition;
- Certificated Insulation controller;
- 1% output current stabilization. Equipment
description
The apparatus is composed by:
1. Input automatic circuit breaker with choke coil;
2. Rectifier;
3. PWM IGBT Inverter;
4. Transformer;
5. Control logic;
6. Parameter and control panel;
7. Continuity and insulation test;
8. Interface module (as option).
Monitoring control system (as
option)
ELITLUCE monitoring control system allows to monitor the status
and the working of street lighting series circuits.
Available functions:
- Display of voltage and current for each regulator: the voltage
value allows to know the fault presence;
- Start up and shut down of the regulators;
- Setting the function of the start up, the shutdown and the
working with reduced flux;
- Detection fault apparatus;
- Detection general alarms: steams, accesses, temperature;
- Power history: start up, shutdown, mains fault, flux reduced
periods, max temperature.
The network offers a simply way to connect the existing infrastructures
(meter sensor, control device for plant or other) allowing
to business government and companies to delegate management
and maintenance.
The net is Server-multi-Client and is based on TCP/IP protocol,
in order to obtain maximum flexibility and every kind of expansion.
The entire System has been developed with Java language, in
order to permit higher compatibility with every kind of apparatus
and any existing operative system.
Either Server or Client can be hosted on PC or MAC, with Windows
or Linux operative systems and with no use restriction.
Connectivity
ELITLUCE manages communication from and to remote devices,
distributed in two ways:
- Physical connections;
- Wireless connections.
These two kinds of connections can be combined at any way,
to use in the better way the available infrastructures for
the application (telephone cable, ADSL/HDSL connections, optic
fiber cable, GSM/GPRS modem, UMTS modem, HSPDA modem).
The System can use two dedicated lines by cable, optic fiber
or it can use a point of access through LAN network or internet
in remote plant allowing the management with automatic calling
or through request of the control device.
The Workstation logs on Central System through LAN or Internet
network allowing the complete compatibility of the System.
ELITLUCE has a Client platform, designed for mobile phones,
with Java ELITMobile platform. It allows to access directly
with the phone to all data of the Server and to perform all
maintenance actions in remote.
The Central System controls every access with login procedure,
classifying them in different levels according the operative
level that you desire to give at each user.
Standards
- EN 60662
- CEI 64-7
- EN 60071-1/2 (CEI 28-5)
- EN 50081-2
- EN 50082-2 |
Protections
- Cut off regulator within 1 second for series circuit interruption.
(Series circuit open);
- Cut off regulator within 1 second for overcurrent higher
than 10% of set up value;
- None stress on lamp electrode during the ignition with ramp
starting;
- Programmable delay to restart from 0 to 10 minutes;
- Self test system.
Technical data
Input
- Voltage:
- Window voltage:
- Frequency:
- Window frequency:
- Power factor at full load:
- Max input current distortion (THiD): |
400V 3F ± 15% 50/60Hz
±10%
0.95
30% |
| - Opzione:
raddrizzatore dodecafase, per avere un contenuto armonico
del 10% |
Output
- Rated power:
- Output constant single phase rated nominal current:
- Current waveform:
- Nominal voltage:
- Nominal voltage:
- Dynamic stability (from shortcircuit to 100% load
withnominal input rated voltage):
- Static stability (for ± 10% input voltage variations):
- Recovery time for 1000V underseries shortcircuit:
- Nominal rated system voltage:
- Insulation ground level: |
see table
20A o 9,6A
sinusoidal
see table
50Hz
±3%
±2%
nearly zero
see table |
| |
• Voltage level
for insulation
• Held voltage toward ground for 60 sec.
to 50Hz:
• Nominal rated voltage of output cables: |
see
table
see table
see table |
|
- Kind of lamps
fed:
| |
H.P. Sodium
Low pressure Sodium
Mercury
Metal halide
Incandescent
Halogen incandescent
Fluorescent
LED
|
|
Miscellaneous
- Minimum efficiency:
- Max ambient temperature (max 8 hrs):
- Minimum ambient temperature:
- Altitude without downgranding:
- Relative humidity (without condensing):
- Noise at 1mt:
- Protection degree:
- Color:
- Dimensions:
- Peso: |
90%
50°C
-10°C
1.000m slm
95%
65dBA
IP 20
RAL 7001
see table
see table |
- Wheels
- Switch at two positions: local/remote
- Settable flux reduction: local/remote set
- Daily clock with functioning cycle:
Ignition with normal flux, working with normal flux,
working with reduced flux, working with normal flux
and shutdown
- Working hour counter |
Insulation controller
- Working: on line
- Measure of insulation resistance.
- Two insulation thresholds (prealarm and alarm) with exchange
contact.
# Lamp series circuits with nominal voltage from 1000V to
6000V (group E circuits) must get an insulation resistance
(Mohm) towards ground not less than:
2x(nominal voltage towards ground in kV of the circuits)
(total
length of lines in km) + (no. lamps)
Commands
- Switch at three positions:
Disconnected - local - remote connected
- Settable flux selector
Normal flux / reduced flux selector Signaling
- Set:
- Regulator:
- Series circuit fault |
local/remote
connected/disconnected |
Measure
- Voltage
- Current
- Insulation resistance (as option) Remote
control
- Connection/disconnection
- Normal flux/reduced flux.
|
|
CONSTANT CURRENT REGULATORS
FOR STREET LIGHTING SERIES CIRCUITS
SERIE ELIGHT |
Rated
power
(kVA) |
30 |
40 |
50 |
60 |
110 |
Current
(A) |
9.6 |
20 |
9.6 |
20 |
9.6 |
20 |
9.6 |
20 |
30/24 |
Nominal
Voltage
(kV) |
3 |
1,5 |
4 |
2 |
5 |
2,5 |
6 |
3 |
6 |
Voltage
level for insulation
(kV) |
3.6 |
3.6 |
7.2 |
3.6 |
7.2 |
3.6 |
7.2 |
3.6 |
7.2 |
Held
voltage
Toward ground
(kV) |
10 |
10 |
20 |
10 |
20 |
10 |
20 |
10 |
20 |
Nominal
voltage
Output cables
(kV) |
2.3/3 |
2.3/3 |
6/10 |
2.3/3 |
6/10 |
2.3/3 |
6/10 |
2.3/3 |
6/10 |
Dimensions
(mm) |
800x800x1800 |
800
x
1000
x
1800 |
Weight
(kgs) |
400 |
450 |
500 |
600 |
900 |
|
| download
pdf |
 |
ask
for a quotation |
 |
|
|
 |
|